APPLICATION
These cables can be used for fixed and mobile equipment connections that are used in offices and kitchens where there
is a risk of contacting with hot surfaces.
CONDUCTOR : Electrolytic annealed, class 5 stranded plain copper wires (tinned conductor on request)
SEPARATOR : A suitable tape may be applied over the conductor
INSULATION : EI4 Type rubber (EPR) compound
CORE IDENTIFICATION : Acc. to HD 308
SHEATH : EM3 Type elastomer compound
COLOR : Black (other colors on request)
CONSTRUCTION : EN 50525-2-21, HD 22.4, DIN VDE 0282-4, BS 6500, BS 7919, IEC 60245-4
GENERAL REQUIREMENTS : EN 50525-1, HD 22.1, DIN VDE 0282-1, IEC 60245-1
GUIDE TO USE : HD 516, DIN VDE 0298-300
ELECTRICAL TESTS : EN 50395, IEC 60245-2
NON-ELECTRICAL TESTS : EN 50396, IEC 60245-2
CONDUCTOR RESISTANCE : EN/IEC 60228, HD 383, DIN VDE 0295, BS 6360
| Güç Damarları | Toprak Damarları | İç Kumanda Damarı | Kılıf | Ağırlıklar | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Kesit mm2 | Büküm no/mm | İletken Çapı Nom. Mm | İzolasyon Kalınlığı mm | İzolasyon Çapı Nom. Mm | Büküm Min.no/mm | Nominal Kesit mm2 | Yarı İletken Kılıf Kalınlığı mm2 | Büküm Min.no/mm | İzolasyon Kalınlığı mm | Kalınlık mm | Kablo Çapı Nom.mm | Yaklaşık Kablo Ağırlığı kg/km | Bakır Ağırlığı kg/km |
| Type 275 1.1/1.1kv | |||||||||||||
| 35 | 285/0,40 | 8.5 | 1.6 | 12.1 | 75/0,40 | 9,4 | 1 | 24/0.20 | 0.8 | 4.3 | 37.9 | 2,600 | 1,286 |
| 50 | 380/0,40 | 10 | 1.7 | 13.4 | 99/0,40 | 12.4 | 1 | 40/0.20 | 0.8 | 4.7 | 41.6 | 3,250 | 1,810 |